Compressor Temperature Error
Compressor temperature error codes by model:
10x Operation & 3x Timer:
RL2 series, RLS3 series, RLS2 series, RLB/RLXB series, RLF series, RLF1 series, LUAS1 series, LMAS series, LZBS series, LZAS series, LPAS series, RGLX series, RLE series
3x Operation & 8x Timer:
RLS series, RLXS series, CQ series, RQ series, R2 series, RL series, RML series, RMLQ series, CLX series, CLX1 series, RLX series, RLXQ series, CL1 series, CL series, RLQ series
(*Operation & Timer LEDs colors are reversed) (**Refer to wired remote controller)
Continuous flash Operation & 8x flashes Timer:
ABU18RULX, ABU24RULX & ABU36RSLX
10x flashes on LED A, 3x flashes on LED B & 1x flash on LED F:
AOU36RLXFZH & AOU45RLXFZ
2x flashes on Power Mode LED, Solid Error LED, 10x flash L1, 3x flash L2, solid L5 & solid L6:
AOU30RLXEH
EA31 outdoor LED:
AOU48RLXFZ & AOU48RLXFZ1
97 / 98 / 1B Wired remote:
UTY-RNBYU, UTY-RNNUM, UTY-RVNUM, UTY-RSNUM, UTY-DMMUM & UTY-RNRUZ series, UTY-RSRY, UTY-RHRY
Compressor Temperature Error Troubleshooting Checklist
Cooling Operation:
- Check of 3-way valve (gas side) was closed, open the 3-way valve and check operation.
- Should that not solve the error, check if the EEV (electronic expansion valve) is defective. Instructions on ohming the EEV out can be found here.
- Conduct a strainer check to see if the strainer is clogged. The strainer does not have temperature difference between the inlet and outlet. If there is a temperature difference as shown in figure 2, there is a possibility the strainer is clogged and would need replacing.
- Inspect the condenser fan motor to see if motor spins freely with little to no resistance. If no problems are found, proceed to ohm the motor windings. Instructions on condenser fan motor checking can be found here. If windings are not within range, motor must be replaced.
- If fan ohms correctly, check the resistance of the Compressor Thermistor by ohming it out. See attached Thermistor Resistance Chart.
- If above does not rectify the system of the error proceed to leak checking the system. Instructions on proper leak checking can be found here.
Heating Operation:
- Check of 3-way valve (liquid side) was closed, open the 3-way valve and check operation.
- Should that not solve the error, check if the EEV (electronic expansion valve) is defective. Instructions on ohming the EEV out can be found here.
- Conduct a strainer check to see if the strainer is clogged. The strainer does not have temperature difference between the inlet and outlet. If there is a temperature difference as shown in figure 2, there is a possibility the strainer is clogged and would need replacing.
- Proceed to checks 4-6 of Cooling Operation checklist to continue.
Disclaimer:
Always Practice Safety First. Turn off power before commencing any work. In order to perform some of these tests an electrical and/or refrigerant license is required. We strongly advise to check the Service manual for more detailed explanation. If you are not sure about these recommendations please contact our technical support line at 866-952-8324. Fujitsu General America, Inc. is not responsible for any damage and/or harm caused by unsafe acts during these test.