Compressor Control Error
Compressor control error codes by model:
9x Operation & 5x Timer flash:
RL2 series, RLS3 series, RLS2 series, RLB/RLXB series, RLF series, RLF1 series, LUAS1 series, LMAS series, LZBS series, LZAS series, LPAS series, RGLX series, RLE series
5x Operation & 5x Timer flash:
RLS series, RLXS series, CQ series, RQ series, R2 series, RL series, RML series, RMLQ series, CLX series, CLX1 series, RLX series, RLXQ series, CL1 series, CL series, RLQ series
13x flashes on LED 1:
AOU18RLXFZ, AOU18RLXFZH, AOU24RLXFZ, AOU24RLXFZH, AOU36RLXFZ, AOU36RLXFZ1, AOU24RML, AOU24RML1, AOU36RML & AOU36RML1
Continuous blink on Operation & 13x flashes on Timer:
ABU18RULX, ABU24RULX & ABU36RSLX
2 flashes on Power Mode LED, Solid Error LED, 9x flashes on L1, 5x flashes on L2, solid L6 LED:
AOU30RLXEH
9x flashes on LED A, 5x flashes on LED B & solid LED F:
AOU36RLXFZH & AOU45RLXFZ
E951:
AOU48RLXFZ & AOU48RLXFZ1
95 / 1A Wired remote:
UTY-RNNUM, UTY-RVNUM, UTB-UUB, UTY-RSNUM, UTY-DMMUM, UTY-RSRY & UTY-RNRUZ Series
Compressor Control / Compressor Location Error Troubleshooting Checklist
- This is a resettable error code, always cycle power off to the disconnect for a full 5 minutes first to see if error code goes away.
- If error code reappears cycle power back off to the disconnect.
- Ohm the compressor windings out. Instructions on how to properly ohm our compressors out can be found here.
- Make sure none of the compressor wires are burnt up or pinched.
- Ohm the condenser fan motor out to make sure the motor windings are intact. instructions on ohming the fan motor can be found here.
- If compressor and fan motor windings ohm within spec, replace the Main Control board, ACTPM and IPM. (If separate from Main Control board.
In troubleshooting the electrical boards you find that one must be replaced, How-To videos can be found here.
Disclaimer:
Always Practice Safety First. Turn off power before commencing any work. In order to perform some of these tests an electrical and/or refrigerant license is required. We strongly advise to check the Service manual for more detailed explanation. If you are not sure about these recommendations please contact our technical support line at 866-952-8324. Fujitsu General America, Inc. is not responsible for any damage and/or harm caused by unsafe acts during these test.